Replacement Refrigerants for Water Chillers
Abstract
The Montreal Protocol requires large water chillers cease using refrigerants 11, 22 and 123. Comparing thermodynamic and transport property parameters for these, 134a, 290, 601, 601a, 717 and pentafiuoroiodoethane avoids certain errors and biases. The parameters for R71 7 (ammonia) offer energy savings about 20%. R290 or 717 can replace 22. The pentane mixture R601 /601a [50/50] with an electronic 38% rotor speed increase can economically replace R11.
References
URL: http://i1m.mech.unsw.edu.au/
Andrews, N. N., 1996, Fluoroiodocarbons for Centrifugal Chillers, BE Project Report, School of Mechanical and Manufacturing Engineering, The University of New South Wales, Kensington, 102 p.
ASHRAE 1996, 1995 ASHRAE Handbook HVAC Systems and Equipment, Chapter 34, American Society of Heating, Refrigerating and Air Conditioning Engineers, Inc., Atlanta.
ASHRAE 1997, 1997 ASHRAE Handbook Fundamentals, Chapter 4, American Society of Heating, Refrigerating and Air Conditioning Engineers, Inc., Atlanta.
Csanady, G. T., 1964, Theory of Turbomachines, McGraw-Hill, New York, 378 p.
Ely, J. F., and Huber, M. L., 1992, NIST Thermophysical Properties of Hydrocarbon Mixtures Database (SUPERTRAPP), Version 1.0, Users' Guide, NIST Standard Reference Database 4, National Institute of Standards and Technology, Gaithersburg MD, July, 44 p.
Environ, 1998, Review of the Toxicity of the Components of Ikon Refrigerant Blends and Recommendations for Acceptable Exposure Limits, Technical Document by ENVIRON Corporation, Arlington VA - for P. Boggs, 14 p.
Holman, J. P., 1992, Heat Transfer, 7th ed. in SI units, McGraw-Hill, London, 713 p.
Huber, M., Gallagher, J., McLinden, M., and Morrison, G., 1996, NIST Thermodynamic Properties of Refrigerants and Refrigerant Mixtures Database (REF-PROP), Version 5.0 Users' Guide, NIST Standard Reference Database 23, U.S=. Department of Commerce, National Institute of Standards and Technology, Gaithersburg MD.
Johnson, C. E. and Derwent, R. G., 1996, Relative Radiative Forcing Consequences of Global Emissions of Hydrocarbons, Carbon Monoxide and NO, from Human Activities Estimated with a Zonally-Averaged Two-Dimensional Model, Climatic Change, vol. 34, pp. 439-462.
Lunde, H. and Lorentzen, G., 1994, Accidents and critical situations due to unintentional escape of refrigerants: a survey of cases in Norway over the last two decades, International Journal of Refrigeration, vol. 17, no. 6, pp. 371-373.
Maclaine-cross, I.L., and Leonardi,"E., 1997, Why hydrocarbons save energy, AIRAH Journal, vol. 51, no. 6, June, pp. 33-38.
Sheets, H". E., 1952, Nondimensional-Compressor Performance for a Range of Mach Numbers and Molecular Weights, Transactions of-the ASME, vol. 93, January, pp. 93-102.